Muller by Beijer Ref · Industrial refrigeration
NKH Series Industrial Unit Cooler
Ceiling-mounted air coolers built for cold stores, blast rooms and food process halls — 75 models across medium and low temperature duties, supplied, installed and serviced in Malaysia by RNA Engineering & Trading Sdn. Bhd.
- Fan diameter
- Ø630 mm · Ø800 mm
- Fans per unit
- 1 to 4
- Fin spacing
- 4 · 6 · 9 mm
- Refrigerants
- R404A / R507 · R22
- Power supply
- 380 V / 3 Ph / 50 Hz
- Motor rating
- IP54, class F
Built for the rooms that never stop running
The NKH Series is Muller's industrial unit cooler for high-duty refrigeration: cold storage warehouses, distribution centres, freezer rooms, seafood and meat processing halls, and process industry rooms where temperature has to hold no matter how often the doors open.
Every unit uses a high-efficiency H-type finned coil — aluminium fins mechanically crimped onto copper tubes — inside a pre-painted galvanised steel casing that resists both corrosion and knocks from forklifts and pallet handling. External rotor fans in Ø630 mm or Ø800 mm sit outside the airstream for easy service, and the whole range ships in reinforced crates already in its mounting position, so it lands on site ready to hang.
With 75 model configurations, one to four fans and three fin spacings, the NKH range lets you match air throw and coil depth to the actual shape of the room instead of oversizing to the nearest catalogue box.
Why specifiers choose the NKH Series
- Compact heat exchangerThe H-type fin gives high capacity from a smaller coil, which also means a faster, cheaper defrost cycle.
- Serviceable by designGalvanised side panels and drain pan are hinge-mounted, and the fans mount externally — cleaning and inspection take minutes.
- Double drain protectionAn internal aluminium drain pan limits condensation dripping below the main pan during defrost.
- Optimised distributionCoils are supplied with diaphragm distributors optimised for R22 and R404A; other refrigerants can be circuited on request.
- Defrost to suit the roomElectric, hot gas, water and shell heaters are all available, with electric defrost standard on low temperature models.
- Wash-down readyStainless steel casing (SSC) versions are available for food processing and corrosive environments.
Typical applications
- Cold storage & frozen distribution — chilled and frozen warehousing, cross-dock chambers, 3PL cold rooms
- Food process industry — chilling halls, packing rooms, meat and seafood processing, bakery retarders
- Blast and holding freezers — down to -30 °C room temperature with 9 mm fin spacing
- Process industry — pharmaceutical and chemical storage, controlled-temperature production areas
How to read an NKH model number
Every digit in the code tells you something about the unit. Read it left to right.
NKH 3 x 6 D B2 R Y - HGT
- NKHH-type high-efficiency fin
- 3Number of fans, 1 to 4
- 6Fan diameter — 6 = 630 mm, 8 = 800 mm
- DMotor connection, Delta
- B2Coil module (B1–B3 for Ø630, C1–C2 for Ø800)
- RFin spacing — R = 4 mm, L and C = 6 mm, S = 9 mm
- YRefrigerant — blank = R22, Y = R404A / R507
- HGTOption code (see the options list below)
Series letters at a glance
| Series | Fin spacing | Duty | Typical room temperature | Standard defrost |
|---|---|---|---|---|
| NKH…R | 4 mm | Medium temperature | +2 °C to +10 °C | Optional electric / hot gas |
| NKH…L | 6 mm | Medium temperature | +2 °C to +10 °C | Optional electric / hot gas |
| NKH…C | 6 mm | Low temperature | -5 °C to -25 °C | Electric defrost standard |
| NKH…S | 9 mm | Low temperature | down to -30 °C | Electric defrost standard |
Option code +ELU adds low-temperature coil and drain-tray electric defrost. Below +2 °C room temperature, electric or hot gas defrost must be used.
Full NKH model list and technical data
All 75 models, with capacity, airflow, air throw, heater load and shipping weight.
Showing all 75 models.
| Model | Capacity kW | Internal volume dm³ |
Coil rows |
Surface m² |
Fans | Air flow m³/h |
Air throw m |
Fan power W |
Current A |
Heaters W |
Weight kg |
|
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| R404A | R22 | |||||||||||
| NKH 1x6 D B3 R | 26.40 | 25.34 | 28.7 | 8 | 156.0 | 1 | 11 650 | 29 | 1 900 | 3.2 | 13 800 | 200 |
| NKH 1x8 D C2 R | 36.90 | 35.42 | 35.9 | 6 | 195.0 | 1 | 17 850 | 35 | 2 000 | 4.0 | 13 500 | 270 |
| NKH 2x6 D B2 R | 47.67 | 45.76 | 43.1 | 6 | 234.0 | 2 | 25 200 | 33 | 3 800 | 6.4 | 19 800 | 300 |
| NKH 3x6 D B1 R | 59.47 | 57.09 | 43.1 | 4 | 234.0 | 3 | 40 950 | 41 | 5 700 | 9.6 | 19 500 | 370 |
| NKH 2x8 D C1 R | 61.34 | 58.89 | 47.9 | 4 | 260.0 | 2 | 39 000 | 39 | 4 000 | 8.0 | 17 400 | 420 |
| NKH 2x8 D C2 R | 72.64 | 69.73 | 71.8 | 6 | 390.0 | 2 | 35 700 | 36 | 4 000 | 8.0 | 26 100 | 480 |
| NKH 3x6 D B2 R | 74.34 | 71.40 | 64.6 | 6 | 351.0 | 3 | 37 800 | 38 | 5 700 | 9.6 | 29 250 | 430 |
| NKH 4x6 D B1 R | 79.71 | 76.52 | 55.7 | 4 | 312.0 | 4 | 54 600 | 46 | 7 600 | 12.8 | 25 800 | 480 |
| NKH 3x8 D C1 R | 81.55 | 78.29 | 69.6 | 4 | 390.0 | 3 | 58 500 | 45 | 6 000 | 12.0 | 25 800 | 570 |
| NKH 4x6 D B2 R | 95.24 | 91.43 | 83.5 | 6 | 468.0 | 4 | 50 400 | 43 | 7 600 | 12.8 | 38 700 | 550 |
| NKH 4x6 D B3 R | 106.83 | 102.56 | 111.3 | 8 | 623.9 | 4 | 46 600 | 40 | 7 600 | 12.8 | 51 600 | 630 |
| NKH 3x8 D C2 R | 107.46 | 103.16 | 104.3 | 6 | 584.9 | 3 | 53 550 | 42 | 6 000 | 12.0 | 38 700 | 670 |
| NKH 4x8 D C2 R | 127.18 | 122.09 | 139.1 | 6 | 779.9 | 4 | 71 400 | 47 | 8 000 | 16.0 | 51 300 | 840 |
| Model | Capacity kW | Internal volume dm³ |
Coil rows |
Surface m² |
Fans | Air flow m³/h |
Air throw m |
Fan power W |
Current A |
Heaters W |
Weight kg |
|
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| R404A | R22 | |||||||||||
| NKH 1x6 D B3 L | 25.41 | 24.39 | 28.7 | 8 | 107.4 | 1 | 12 600 | 31 | 1 900 | 3.2 | 13 800 | 190 |
| NKH 1x8 D C2 L | 34.39 | 33.01 | 35.9 | 6 | 134.3 | 1 | 19 200 | 38 | 2 000 | 4.0 | 13 500 | 260 |
| NKH 2x6 D B1 L | 35.26 | 33.85 | 28.7 | 4 | 107.2 | 2 | 28 600 | 37 | 3 800 | 6.4 | 13 200 | 260 |
| NKH 2x6 D B3 L | 50.99 | 48.95 | 57.5 | 8 | 214.4 | 2 | 25 200 | 33 | 3 800 | 6.4 | 26 400 | 330 |
| NKH 2x8 D C1 L | 54.64 | 52.45 | 47.9 | 4 | 179.0 | 2 | 41 300 | 41 | 4 000 | 8.0 | 17 400 | 400 |
| NKH 2x8 D C2 L | 68.11 | 65.39 | 71.8 | 6 | 268.5 | 2 | 38 400 | 38 | 4 000 | 8.0 | 26 100 | 460 |
| NKH 3x6 D B2 L | 68.38 | 65.64 | 64.6 | 6 | 241.2 | 3 | 40 200 | 40 | 5 700 | 9.6 | 29 250 | 410 |
| NKH 3x6 D B3 L | 75.77 | 72.74 | 86.2 | 8 | 332.3 | 3 | 37 800 | 38 | 5 700 | 9.6 | 39 000 | 460 |
| NKH 4x6 D B2 L | 88.61 | 85.07 | 83.5 | 6 | 322.2 | 4 | 53 600 | 46 | 7 600 | 12.8 | 38 700 | 530 |
| NKH 3x8 D C2 L | 100.68 | 96.65 | 104.3 | 6 | 402.8 | 3 | 57 600 | 45 | 6 000 | 12.0 | 38 700 | 650 |
| NKH 4x6 D B3 L | 102.39 | 98.29 | 111.3 | 8 | 428.9 | 4 | 50 400 | 43 | 7 600 | 12.8 | 51 600 | 600 |
| NKH 4x8 D C2 L | 119.66 | 114.87 | 139.1 | 6 | 536.3 | 4 | 76 800 | 50 | 8 000 | 16.0 | 51 300 | 800 |
| Model | Capacity kW | Internal volume dm³ |
Coil rows |
Surface m² |
Fans | Air flow m³/h |
Air throw m |
Fan power W |
Current A |
Heaters W |
Weight kg |
|
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| R404A | R22 | |||||||||||
| NKH 1x6 D B3 C | 19.86 | 19.07 | 28.7 | 8 | 107.4 | 1 | 12 600 | 31 | 1 900 | 3.2 | 13 800 | 210 |
| NKH 1x8 D C2 C | 26.02 | 24.98 | 35.9 | 6 | 134.3 | 1 | 19 200 | 38 | 2 000 | 4.0 | 13 500 | 280 |
| NKH 2x6 D B1 C | 26.31 | 25.26 | 28.7 | 4 | 107.2 | 2 | 28 600 | 37 | 3 800 | 6.4 | 13 200 | 290 |
| NKH 2x6 D B2 C | 34.50 | 33.12 | 41.3 | 6 | 161.1 | 2 | 26 800 | 35 | 3 800 | 6.4 | 19 800 | 320 |
| NKH 2x6 D B3 C | 40.23 | 38.62 | 57.5 | 8 | 214.4 | 2 | 25 200 | 33 | 3 800 | 6.4 | 26 400 | 360 |
| NKH 2x8 D C1 C | 41.67 | 40.00 | 47.9 | 4 | 179.0 | 2 | 41 300 | 41 | 4 000 | 8.0 | 17 400 | 440 |
| NKH 3x6 D B2 C | 51.95 | 49.87 | 64.6 | 6 | 241.2 | 3 | 40 200 | 40 | 5 700 | 9.6 | 29 250 | 460 |
| NKH 3x6 D B3 C | 60.50 | 58.08 | 86.2 | 8 | 322.3 | 3 | 37 800 | 38 | 5 700 | 9.6 | 39 000 | 520 |
| NKH 3x8 D C2 C | 68.49 | 65.75 | 104.3 | 6 | 402.3 | 3 | 57 600 | 45 | 6 000 | 12.0 | 38 700 | 700 |
| NKH 4x6 D B3 C | 70.22 | 67.41 | 111.3 | 8 | 428.9 | 4 | 50 400 | 43 | 7 600 | 12.8 | 51 600 | 670 |
| Model | Capacity kW — SC3 | Capacity kW — SC4 | Internal volume dm³ |
Coil rows |
Surface m² |
Fans | Air flow m³/h |
Air throw m |
Fan power W |
Current A |
Heaters W |
Weight kg |
||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| R404A | R22 | R404A | R22 | |||||||||||
| NKH 1x6 D B3 S | 17.84 | 17.13 | 14.10 | 13.54 | 28.7 | 8 | 74.9 | 1 | 13 400 | 33 | 1 900 | 3.2 | 13 800 | 210 |
| NKH 2x6 D B1 S | 22.44 | 21.54 | 17.57 | 16.87 | 28.7 | 4 | 74.9 | 2 | 29 600 | 38 | 3 800 | 6.4 | 13 200 | 280 |
| NKH 1x8 D C2 S | 22.92 | 22.00 | 18.02 | 17.30 | 35.9 | 6 | 93.6 | 1 | 20 150 | 39 | 2 000 | 4.0 | 13 500 | 280 |
| NKH 2x8 D C1 S | 35.27 | 33.86 | 27.80 | 26.69 | 47.9 | 4 | 124.8 | 2 | 42 800 | 43 | 4 000 | 8.0 | 17 400 | 430 |
| NKH 2x6 D B3 S | 36.08 | 34.64 | 28.56 | 27.42 | 57.5 | 8 | 149.8 | 2 | 26 800 | 35 | 3 800 | 6.4 | 26 400 | 360 |
| NKH 2x8 D C2 S | 40.85 | 39.22 | 31.45 | 30.19 | 71.8 | 6 | 187.2 | 2 | 40 300 | 40 | 4 000 | 8.0 | 26 100 | 480 |
| NKH 3x6 D B2 S | 45.47 | 43.65 | 35.82 | 34.39 | 64.6 | 6 | 168.5 | 3 | 42 150 | 42 | 5 700 | 9.6 | 29 250 | 450 |
| NKH 3x8 D C1 S | 45.80 | 43.97 | 35.01 | 33.61 | 69.6 | 4 | 187.2 | 3 | 64 200 | 50 | 6 000 | 12.0 | 25 800 | 590 |
| NKH 3x6 D B3 S | 54.36 | 52.19 | 43.07 | 41.35 | 86.2 | 8 | 224.7 | 3 | 40 200 | 40 | 5 700 | 9.6 | 39 000 | 510 |
| NKH 3x8 D C2 S | 60.62 | 58.20 | 46.63 | 44.76 | 104.3 | 6 | 280.8 | 3 | 60 450 | 47 | 6 000 | 12.0 | 38 700 | 670 |
| NKH 4x6 D B3 S | 63.76 | 61.21 | 49.19 | 47.22 | 111.3 | 8 | 299.5 | 4 | 53 600 | 46 | 7 600 | 12.8 | 51 600 | 640 |
| NKH 4x8 D C2 S | 76.19 | 73.14 | 57.79 | 55.48 | 139.1 | 6 | 374.4 | 4 | 80 600 | 53 | 8 000 | 16.0 | 51 300 | 860 |
| Model | Capacity kW R404A |
Internal volume dm³ |
Coil rows |
Surface m² |
Fans | Air flow m³/h |
Air throw m |
Fan power W |
Current A |
Heaters W |
Weight kg |
|---|---|---|---|---|---|---|---|---|---|---|---|
| NKH 1x6 D B2 RY-CCS | 17.1 | 20 | 6 | 72.0 | 1 | 12 000 | 30 | 1 600 | 3.2 | 9 000 | 123 |
| NKH 1x6 D B3 RY-CCS | 19.5 | 27 | 8 | 104.0 | 1 | 11 200 | 29 | 1 600 | 3.2 | 9 000 | 145 |
| NKH 2x6 D B2 RY-CCS | 31.6 | 39 | 6 | 156.0 | 2 | 24 600 | 32 | 3 200 | 6.4 | 10 800 | 243 |
| NKH 2x6 D B3 RY-CCS | 38.3 | 53 | 8 | 208.0 | 2 | 22 500 | 31 | 3 200 | 6.4 | 10 800 | 288 |
| NKH 3x6 D B2 RY-CCS | 47.9 | 59 | 6 | 234.0 | 3 | 36 900 | 34 | 4 800 | 9.6 | 16 200 | 330 |
| NKH 3x6 D B3 RY-CCS | 58.6 | 79 | 8 | 312.0 | 3 | 33 750 | 33 | 4 800 | 9.6 | 16 200 | 400 |
| NKH 4x6 D B2 RY-CCS | 63.8 | 71 | 6 | 280.0 | 4 | 49 000 | 34 | 6 400 | 12.8 | 29 250 | 430 |
| NKH 4x6 D B3 RY-CCS | 70.7 | 95 | 8 | 374.0 | 4 | 43 000 | 33 | 6 400 | 12.8 | 29 250 | 480 |
| NKH 3x8 D C1 RY-CCS | 73.5 | 95 | 6 | 373.0 | 3 | 59 100 | 60 | 6 000 | 12.0 | 39 000 | 550 |
| NKH 3x8 D C2 RY-CCS | 90.1 | 95 | 8 | 499.0 | 3 | 56 900 | 58 | 6 000 | 12.0 | 39 000 | 620 |
| Model | Capacity kW R404A |
Internal volume dm³ |
Coil rows |
Surface m² |
Fans | Air flow m³/h |
Air throw m |
Fan power W |
Current A |
Heaters W |
Weight kg |
|---|---|---|---|---|---|---|---|---|---|---|---|
| NKH 1x6 D B2 CY-CCS | 14.5 | 20 | 6 | 52.0 | 1 | 13 000 | 31 | 1 600 | 3.2 | 9 000 | 123 |
| NKH 1x6 D B3 CY-CCS | 16.8 | 27 | 8 | 70.0 | 1 | 12 000 | 30 | 1 600 | 3.2 | 9 000 | 145 |
| NKH 2x6 D B2 CY-CCS | 25.9 | 39 | 6 | 104.0 | 2 | 26 100 | 34 | 3 200 | 6.4 | 10 800 | 243 |
| NKH 2x6 D B3 CY-CCS | 30.0 | 53 | 8 | 139.0 | 2 | 24 000 | 32 | 3 200 | 6.4 | 10 800 | 288 |
| NKH 3x6 D B2 CY-CCS | 37.2 | 59 | 6 | 156.0 | 3 | 39 150 | 36 | 4 800 | 9.6 | 16 200 | 325 |
| NKH 3x6 D B3 CY-CCS | 45.8 | 79 | 8 | 209.0 | 3 | 36 000 | 34 | 4 800 | 9.6 | 16 200 | 393 |
| NKH 4x6 D B2 CY-CCS | 47.8 | 71 | 6 | 188.0 | 4 | 51 000 | 36 | 6 400 | 12.8 | 29 250 | 410 |
| NKH 4x6 D B3 CY-CCS | 55.6 | 95 | 8 | 250.0 | 4 | 44 700 | 34 | 6 400 | 12.8 | 29 250 | 477 |
| NKH 3x8 D C1 CY-CCS | 60.7 | 95 | 6 | 95.0 | 3 | 62 000 | 62 | 6 000 | 12.0 | 39 000 | 545 |
| NKH 3x8 D C2 CY-CCS | 70.3 | 126 | 8 | 126.0 | 3 | 60 400 | 60 | 6 000 | 12.0 | 39 000 | 610 |
| Model | Capacity kW SC3, R404A |
Capacity kW SC4, R404A |
Internal volume dm³ |
Coil rows |
Surface m² |
Fans | Air flow m³/h |
Air throw m |
Fan power W |
Current A |
Heaters W |
Weight kg |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NKH 2x6 D B2 SY-CCS | 16.50 | 13.60 | 39 | 6 | 96 | 2 | 27 600 | 38 | 3 200 | 6.4 | 16 200 | 250 |
| NKH 2x6 D B3 SY-CCS | 22.00 | 18.20 | 53 | 8 | 128 | 2 | 26 800 | 37 | 3 200 | 6.4 | 16 200 | 326 |
| NKH 3x6 D B2 SY-CCS | 24.70 | 20.40 | 59 | 6 | 144 | 3 | 41 400 | 40 | 4 800 | 9.6 | 24 300 | 358 |
| NKH 3x6 D B3 SY-CCS | 32.60 | 30.60 | 79 | 8 | 192 | 3 | 40 200 | 39 | 4 800 | 9.6 | 24 300 | 415 |
| NKH 4x6 D B2 SY-CCS | 32.90 | 32.00 | 71 | 6 | 172 | 4 | 55 000 | 40 | 6 400 | 12.8 | 29 250 | 505 |
| NKH 4x6 D B3 SY-CCS | 42.70 | 35.20 | 95 | 8 | 230 | 4 | 53 000 | 39 | 6 400 | 12.8 | 29 250 | 522 |
| NKH 3x8 D C1 SY-CCS | 43.50 | 36.00 | 95 | 6 | 230 | 3 | 63 800 | 60 | 6 000 | 12.0 | 39 000 | 656 |
| NKH 3x8 D C2 SY-CCS | 55.30 | 45.80 | 127 | 8 | 306 | 3 | 61 600 | 58 | 6 000 | 12.0 | 39 000 | 678 |
Fan data at 380 V / 3 Ph / 50 Hz in delta connection. Residual air speed 0.5 m/s in compliance with standard. For star (Y) connection instead of delta (D), apply the correction factors below. Heater load shown is the electric defrost kit at 380 V / 3 Ph / 50 Hz.
Defrost options
NKH…C and NKH…S — low temperature
Shielded electric heating elements sit in sleeves inside the finned coil, with two or three further elements under the intermediate drain pan. Heat is distributed evenly for a fast, clean defrost, and the heaters are factory-wired to a 380 V / 3 Ph terminal block in a junction box. Total hot gas defrost (HGT) is available as an option.
NKH…R and NKH…L — medium temperature
Low-temperature electric defrost (ELU) is available as an optional extra. Water defrost (DAE) can be used where room temperature is +4 °C or above; specifying it increases the unit cooler depth by 40 mm.
Maximum water flow rate: 5 m³/h for 1 fan, 10 m³/h for 2 fans, 15 m³/h for 3 fans, 20 m³/h for 4 fans.
Options and accessories
| Option | NKH…R / L — medium temp | NKH…C / S — low temp |
|---|---|---|
| ZIEHL-ABEGG motor | ● | ● |
| Interlink motor | ✕ | ✕ |
| EBM EC motor | ✕ | ✕ |
| Blue fin coating | ○ | ○ |
| Black electrophoresis fin coating | ✕ | ✕ |
| Pre-tinned galvanised steel casing | ● | ● |
| Stainless steel casing (SSC) | ○ | ○ |
| Electric defrost (ELU) | ○ | ● |
| Hot gas defrost, coil and tray (HGT) | ○ | ○ |
| Water defrost (DAE) | ○ | ✕ |
| Shell defrost heaters (RVU) | ○ | ○ |
| 4 mm fin spacing (…R) | ● | ✕ |
| 6 mm fin spacing (…L) | ● | ✕ |
| 6 mm fin spacing (…C) | ✕ | ● |
| 9 mm fin spacing (…S) | ✕ | ● |
| Factory fan wiring (CMU) | ○ | ○ |
| 60 Hz fans, 230–400 V / 3 Ph (M60) | ○ | ○ |
| Air pressure shell (VAP) | ○ | ○ |
| Glycol water extension (EGU) | ○ | ○ |
| Coil paint protection (BAE) | ○ | ○ |
The VAP air pressure shell increases air throw significantly — from roughly 29–53 m on a standard unit to 44–68 m — which is worth specifying for deep racking runs. Configurations not listed here can usually be built; ask us.
Dimensions and connections
Ø630 mm fan units
| Fans | Overall length mm | Depth D mm | Height H mm |
|---|---|---|---|
| 1 fan (NKH 1x6) | 1 665 | 550 | 1 115 |
| 2 fans (NKH 2x6) | 2 865 | 700 | 1 115 |
| 3 fans (NKH 3x6) | 4 065 | 800 | 1 158 |
| 4 fans (NKH 4x6) | 5 265 | 850 | 1 158 |
Ø800 mm fan units
| Fans | Overall length mm | Depth D mm | Height H mm |
|---|---|---|---|
| 1 fan (NKH 1x8) | 2 115 | 700 | 1 375 |
| 2 fans (NKH 2x8) | 3 715 | 900 | 1 375 |
| 3 fans (NKH 3x8) | 5 315 | 1 000 | 1 375 |
| 4 fans (NKH 4x8) | 6 915 | 1 050 | 1 375 |
Connection sizes — Ø630 mm range
| Model | Liquid inlet mm | Suction outlet mm | Drain mm |
|---|---|---|---|
| NKH 1x6 D B3 R | 28.6 | 41.3 | 47.6 |
| NKH 2x6 D B2 R | 34.9 | 54.0 | 47.6 |
| NKH 3x6 D B1 R | 41.3 | 2×54.0 | 47.6 |
| NKH 3x6 D B2 R | 2×34.9 | 2×54.0 | 47.6 |
| NKH 4x6 D B1 R | 2×41.3 | 2×54.0 | 47.6 |
| NKH 4x6 D B2 R | 2×34.9 | 2×54.0 | 47.6 |
| NKH 4x6 D B3 R | 2×41.3 | 2×54.0 | 47.6 |
| NKH 1x6 D B3 L | 28.6 | 41.3 | 47.6 |
| NKH 2x6 D B1 L | 34.9 | 54.0 | 47.6 |
| NKH 2x6 D B3 L | 41.3 | 54.0 | 47.6 |
| NKH 3x6 D B2 L | 2×34.9 | 2×54.0 | 47.6 |
| NKH 3x6 D B3 L | 41.3 | 66.7 | 47.6 |
| NKH 4x6 D B2 L | 2×34.9 | 2×54.0 | 47.6 |
| NKH 4x6 D B3 L | 2×41.3 | 2×54.0 | 47.6 |
| NKH 1x6 D B3 C | 28.6 | 54.0 | 47.6 |
| NKH 2x6 D B1 C | 34.9 | 54.0 | 47.6 |
| NKH 2x6 D B2 C | 41.3 | 66.7 | 47.6 |
| NKH 2x6 D B3 C | 41.3 | 66.7 | 47.6 |
| NKH 3x6 D B2 C | 2×34.9 | 2×54.0 | 47.6 |
| NKH 3x6 D B3 C | 2×41.3 | 2×54.0 | 47.6 |
| NKH 4x6 D B3 C | 2×41.3 | 2×66.7 | 47.6 |
| NKH 1x6 D B3 S | 28.6 | 54.0 | 47.6 |
| NKH 2x6 D B1 S | 34.9 | 54.0 | 47.6 |
| NKH 2x6 D B3 S | 34.9 | 66.7 | 47.6 |
| NKH 3x6 D B2 S | 2×28.6 | 2×54.0 | 47.6 |
| NKH 3x6 D B3 S | 2×34.9 | 2×54.0 | 47.6 |
| NKH 4x6 D B3 S | 2×41.3 | 2×66.7 | 47.6 |
Connection sizes — Ø800 mm range
| Model | Liquid inlet mm | Suction outlet mm | Drain mm |
|---|---|---|---|
| NKH 1x8 D C2 R | 34.9 | 54.0 | 47.6 |
| NKH 2x8 D C1 R | 41.3 | 66.7 | 47.6 |
| NKH 2x8 D C2 R | 41.3 | 66.7 | 47.6 |
| NKH 3x8 D C1 R | 41.3 | 66.7 | 47.6 |
| NKH 3x8 D C2 R | 2×41.3 | 2×54.0 | 47.6 |
| NKH 4x8 D C2 R | 2×41.3 | 2×66.7 | 47.6 |
| NKH 1x8 D C2 L | 34.9 | 54.0 | 47.6 |
| NKH 2x8 D C1 L | 41.3 | 54.0 | 47.6 |
| NKH 2x8 D C2 L | 41.3 | 66.7 | 47.6 |
| NKH 3x8 D C2 L | 2×41.3 | 2×54.0 | 47.6 |
| NKH 4x8 D C2 L | 2×41.3 | 2×54.0 | 47.6 |
| NKH 1x8 D C2 C | 34.9 | 54.0 | 47.6 |
| NKH 2x8 D C1 C | 41.3 | 66.7 | 47.6 |
| NKH 3x8 D C2 C | 2×41.3 | 2×66.7 | 47.6 |
| NKH 1x8 D C2 S | 34.9 | 54.0 | 47.6 |
| NKH 2x8 D C1 S | 41.3 | 66.7 | 47.6 |
| NKH 2x8 D C2 S | 41.3 | 66.7 | 47.6 |
| NKH 3x8 D C1 S | 41.3 | 66.7 | 47.6 |
| NKH 3x8 D C2 S | 2×41.3 | 2×54.0 | 47.6 |
| NKH 4x8 D C2 S | 2×41.3 | 2×66.7 | 47.6 |
Stainless steel range connections
| Model | Liquid inlet | Suction outlet | Drain |
|---|---|---|---|
| NKH 1x6 D B2 RY-CCS / CY-CCS | 5/8" | 1 1/8" | G2' |
| NKH 1x6 D B3 RY-CCS / CY-CCS | 7/8" | 1 5/8" | G2' |
| NKH 2x6 D B2 RY-CCS / CY-CCS | 7/8" | 1 5/8" | G2' |
| NKH 2x6 D B3 RY-CCS / CY-CCS | 1 1/8" | 2 1/8" | G2' |
| NKH 3x6 D B2 RY-CCS | 1 1/8" | 2 1/8" | G2' |
| NKH 3x6 D B2 CY-CCS | 1 3/8" | 2 1/8" | G2' |
| NKH 3x6 D B3 RY-CCS | 1 1/8" | 2 1/8" | G2' |
| NKH 3x6 D B3 CY-CCS | 1 3/8" | 2 1/8" | G2' |
| NKH 4x6 D B2 RY-CCS / CY-CCS | 1 3/8" | 2 1/8" | G2' |
| NKH 4x6 D B3 RY-CCS / CY-CCS | 1 3/8" | 2 1/8" | G2' |
| NKH 3x8 D C1 RY-CCS / CY-CCS | 1 1/8" | 2 1/8" | G2' |
| NKH 3x8 D C2 RY-CCS / CY-CCS | 1 3/8" | 2 5/8" | G2' |
| NKH 2x6 D B2 SY-CCS | 7/8" | 1 5/8" | G2' |
| NKH 2x6 D B3 SY-CCS | 1 1/8" | 2 1/8" | G2' |
| NKH 3x6 D B2 SY-CCS | 7/8" | 1 5/8" | G2' |
| NKH 3x6 D B3 SY-CCS | 7/8" | 1 5/8" | G2' |
| NKH 4x6 D B2 SY-CCS | 1 1/8" | 2 1/8" | G2' |
| NKH 4x6 D B3 SY-CCS | 1 1/8" | 2 1/8" | G2' |
| NKH 3x8 D C1 SY-CCS | 1 1/8" | 2 1/8" | G2' |
| NKH 3x8 D C2 SY-CCS | 1 3/8" | 2 5/8" | G2' |
Liquid and suction dimensions are the product inlet and outlet sizes only. Calculate the actual connecting pipe diameter from your own system design.
Sound power level
| Fan diameter | 1 fan D / Y | 2 fans D / Y | 3 fans D / Y | 4 fans D / Y |
|---|---|---|---|---|
| Ø630 mm | 90 / 82 | 93 / 85 | 95 / 87 | 96 / 88 |
| Ø800 mm | 84 / 77 | 87 / 80 | 89 / 82 | 90 / 83 |
Ø800 mm fans run at 1 000 rpm on 6 poles and are noticeably quieter than the 1 500 rpm 4-pole Ø630 mm fans — useful where the cold room adjoins occupied space.
Capacity correction factors
Actual capacity = catalogue capacity × correction factor × (actual TD ÷ rated TD).
Room temperature factors
| Room °C | -5 | -2 | 0 | +2 | +4 | +6 | +8 | +10 |
|---|---|---|---|---|---|---|---|---|
| Factor | 0.98 | 0.99 | 1.00 | 1.07 | 1.14 | 1.17 | 1.17 | 1.17 |
| Room °C | -24 | -22 | -20 | -18 | -16 | -14 | -10 | -5 |
|---|---|---|---|---|---|---|---|---|
| Factor | 0.97 | 0.98 | 0.99 | 1.00 | 1.01 | 1.02 | 1.04 | 1.06 |
| Room °C | -30 | -26 | -24 | -22 | -18 | -14 | -10 | -5 |
|---|---|---|---|---|---|---|---|---|
| Factor | 0.92 | 0.92 | 0.97 | 0.98 | 1.00 | 1.02 | 1.04 | 1.06 |
Star (Y) motor connection factors
| Module | 4 mm fin spacing | 6 mm fin spacing | 9 mm fin spacing | ||||||
|---|---|---|---|---|---|---|---|---|---|
| Air flow | Capacity | Air throw | Air flow | Capacity | Air throw | Air flow | Capacity | Air throw | |
| NKH-B1 | 0.76 | 0.87 | 0.76 | 0.76 | 0.87 | 0.76 | 0.76 | 0.89 | 0.76 |
| NKH-B2 | 0.76 | 0.86 | 0.76 | 0.76 | 0.85 | 0.76 | 0.76 | 0.87 | 0.76 |
| NKH-B3 | 0.76 | 0.85 | 0.76 | 0.76 | 0.84 | 0.76 | 0.76 | 0.86 | 0.76 |
| NKH-C1 | 0.73 | 0.85 | 0.73 | 0.74 | 0.84 | 0.74 | 0.74 | 0.86 | 0.74 |
| NKH-C2 | 0.72 | 0.82 | 0.72 | 0.72 | 0.82 | 0.72 | 0.73 | 0.85 | 0.74 |
Capacities are rated to Eurovent standards. Refrigerant capacity factors are calculated from current refrigerant manufacturer thermodynamic data and the Beijer Ref coil rating program. For duties outside these limits, contact us — distributor, circuiting and defrost characteristics may need to change.
Common questions
What fin spacing should I choose?
Use 4 mm (R) for chilled rooms above 0 °C with light frost loading, 6 mm (L or C) for general chill and medium-low temperature rooms, and 9 mm (S) for freezer and blast rooms down to -30 °C. Wider spacing costs some surface area but holds capacity much longer between defrost cycles in high-humidity, high-traffic rooms.
Is electric defrost standard?
Yes on the low temperature C and S models. On medium temperature R and L models it is an option, alongside hot gas, water and shell defrost heaters. Any room running below +2 °C needs electric or hot gas defrost.
Can I get a stainless steel unit for a wash-down area?
Yes. Stainless steel casing (SSC) models are available in 4.5 mm, 7 mm and 9 mm fin spacing with R404A ratings, and are the usual choice for meat, poultry and seafood processing halls.
Which refrigerants are supported?
Coils ship with diaphragm distributors optimised for R22 and R404A / R507. Other refrigerants can be accommodated, but the distributor and circuiting need to be matched — specify the refrigerant when you order.
How far will the air throw?
Between 29 m and 62 m depending on model, and up to 68 m with the VAP air pressure shell fitted. Match the throw to the length of the room so the far end holds temperature without a second unit.
What is the lead time and who installs it?
Units ship in reinforced crates in their mounting position. RNA Engineering & Trading supplies, commissions and services the NKH range across Malaysia. Send us your room dimensions, product load and design temperatures and we will size it and quote.