Share:


Muller KRC Air Cooled Condenser



MULLER • KRC SERIES

Muller KRC Air Cooled Condenser

Commercial remote air cooled condenser range designed for supermarket, cold storage and commercial refrigeration applications. The KRC series combines flexible top or side ventilation, high-performance condenser coils and multiple fan configurations for a wide range of refrigeration duties.

14 Models 12–258 kW Range R404A R22 R134a R410A 350 / 500 / 630 mm Fans Top / Side Ventilation
Wide Range • Flexible Application Muller KRC commercial air cooled condensers provide a flexible heat-rejection solution for supermarket and cold-storage refrigeration. Multiple coil sizes, fan diameters and airflow arrangements allow the condenser to be matched to different system capacities, site layouts and acoustic requirements.

📋 KRC Series Overview

14 Models KRC80 through KRC861
12–258 kW Catalogue operating range
350–630 mm Axial fan diameters
220 V / 1 Phase Electrical data shown in catalogue

🏪 Designed for Commercial Refrigeration

The KRC range is primarily positioned for supermarket and cold-storage applications, with flexible condenser configurations for remote commercial refrigeration installations.

✨ Key Features

🛡️

Powder-Coated Panels

Panels are powder coated for long service life and improved corrosion resistance.

↕️

Flexible Installation

Units can be installed vertically or horizontally to support top or side ventilation.

🌬️

External Rotor Fans

Quality external rotor motor fans provide long operating life and convenient servicing.

🔇

Low-Noise Possibilities

Fan selections are available for noise-sensitive applications, including two-speed fan arrangements.

♨️

Inner-Grooved Tubes

Optimised condenser coil design incorporates inner-grooved tubing to enhance heat transfer.

🧊

9000 Series Coil Technology

9000 Series coil technology is applied to the inline four-fan module design.

🔧

Leak-Free Header Design

Header clearance holes help the end and divider plate areas remain free from potential leak zones.

📐

Adjustable Euro Legs

Euro leg design allows height adjustment for vertical-airflow configurations.

⚙️

Deep-Spun Venturi

Deep-spun venturi construction is used to maximise fan performance.

🌬️ Fan Configurations

4-Pole AC Fan – 4P

Single-phase fan configuration used across selected smaller and medium KRC models.

350 mm Fans 500 mm Fans Single Phase

6-Pole AC Fan – 6P

Single-phase fan platform with two-speed capability for selected commercial condenser models.

500 mm Fans 630 mm Fans Two-Speed Option

🔎 KRC Model Nomenclature

KRC80C-4PHS-C
KRC Air cooled condenser series
80 Capacity Watts per Degree TD / 10
Option Code Regular option / RMS configuration
4P / 6P 4-pole or 6-pole AC fan
H High-pressure capable R410A coil
S Special non-regular option / combination
C China
Blank Option Standard catalogue configuration

📊 Complete Technical Performance

View All 14 KRC Models – Capacity, Airflow & Electrical Data
Model R404A
W/K
R22
W/K
R134a
W/K
R410A
W/K
Airflow
m³/h
Fan Ø
mm
Fans Phase Current
A
Voltage Total Power
W
Max Current
A
KRC80-4PH-C 803 762 746 819 4,536 350 2 0.58 220-1 260 1.16
KRC107-4PH-C 1,076 1,022 1,001 1,097 4,662 350 2 0.58 220-1 260 1.16
KRC134-4PH-C 1,338 1,271 1,245 1,365 4,356 350 2 0.58 220-1 260 1.16
KRC137-6PH-C 1,366 1,298 1,271 1,394 3,942 500 1 1.35 220-1 290 1.35
KRC181-6PH-C 1,807 1,717 1,681 1,843 8,766 500 2 1.35 220-1 580 2.70
KRC254-6PH-C 2,544 2,417 2,366 2,595 7,812 500 2 1.35 220-1 580 2.70
KRC164-4PH-C 1,635 1,553 1,520 1,667 5,508 500 1 2.80 220-1 640 2.80
KRC213-4PH-C 2,135 2,029 1,986 2,178 11,844 500 2 2.80 220-1 1,280 5.60
KRC317-4PH-C 3,171 3,012 2,949 3,234 10,476 500 2 2.80 220-1 1,280 5.60
KRC389-6PH-C 3,885 3,691 3,613 3,963 13,482 630 2 2.62 220-1 1,200 5.24
KRC457-6PH-C 4,572 4,343 4,252 4,663 23,310 630 3 2.62 220-1 1,800 7.86
KRC574-6PH-C 5,738 5,452 5,337 5,853 20,232 630 3 2.62 220-1 1,800 7.86
KRC693-6PH-C 6,927 6,580 6,442 7,065 31,518 630 4 2.62 220-1 2,400 10.48
KRC861-6PH-C 8,611 8,180 8,008 8,783 27,918 630 4 2.62 220-1 2,400 10.48
Catalogue Capacity Basis:
Capacity data is based on 0 K subcooling, 32°C ambient temperature and 18 K temperature difference (KTD). KTD is the saturated temperature at the condenser outlet minus inlet air / ambient temperature. Minimum actual KTD is 3 K.

Electrical data is based on the fan motor operating at 100% speed.
🧊 Coil Data, Refrigerant Charge & Connection Sizes
Model Rows FPI R404A Charge R410A Charge Inlet Outlet
KRC80-4PH-C 3 10 1.8 1.9 15.9 12.7
KRC107-4PH-C 4 10 3.0 3.1 15.9 12.7
KRC134-4PH-C 6 10 5.4 5.6 19 15.9
KRC137-6PH-C 6 10 5.4 5.6 19 15.9
KRC181-6PH-C 3 10 4.5 4.6 22.2 19
KRC254-6PH-C 6 10 10.2 10.5 25.4 22.2
KRC164-4PH-C 6 10 5.4 5.6 19 15.9
KRC213-4PH-C 3 10 4.5 4.6 22.2 19
KRC317-4PH-C 6 10 10.2 10.5 25.4 22.2
KRC389-6PH-C 5 10 11.4 11.8 31.8 28.6
KRC457-6PH-C 3 10 10.4 10.7 34.9 31.8
KRC574-6PH-C 5 10 17.3 17.9 34.9 31.8
KRC693-6PH-C 3 10 19.1 19.7 38.1 38.1
KRC861-6PH-C 5 10 31.8 32.7 38.1 38.1
Pump-down charge basis in the catalogue: approximately 80% liquid and 20% vapour inside the coil at 55°C condensing temperature.
🔇 Sound Power & Sound Pressure Data
Model Group Sound Power LwA dBA Sound Pressure LpA dBA @ 3m Noise Ratio
KRC80 / KRC107 / KRC134 77 59.5 54
KRC137 75.8 58.3 52
KRC181 / KRC254 78.8 61.3 55
KRC164 81 63.5 59
KRC213 / KRC317 84 66.5 62
KRC389 78.8 61.3 58
KRC457 / KRC574 80.6 63.1 60
KRC693 / KRC861 81.8 64.3 62
💧 Pump-Down Charge Conversion Factors
Refrigerant R404A R507 R410A R134a R407C
Conversion Factor to R404A 1.00 1.05 1.03 1.24 1.13
-5°C SST / 40°C SCT Operating Charge : Pump-Down Charge 0.34 0.35 0.35 0.21 0.26

📐 Complete Dimensions & Weight

View Complete KRC Dimensional Table
Model A B C D E F G H J K L M N W Transport
m³
Net Weight
kg
With Packaging
kg
KRC80-4PH-C 452 48 80 470 500 443 390 705 40 165 951 877 25 927 0.247 29 34
KRC107-4PH-C 452 48 80 570 500 520 390 705 40 165 951 877 25 927 0.299 34 39
KRC134-4PH-C 452 48 80 670 500 647 390 725 40 165 951 877 25 927 0.351 46 51
KRC137-6PH-C 452 48 80 670 500 647 390 745 40 165 951 877 25 927 0.373 51 56
KRC181-6PH-C 766 54 75 849 500 788 605 1020 62 220 1262 1165 38 1241 0.692 68 85
KRC254-6PH-C 766 54 75 954 500 915 605 1020 62 255 1262 1165 38 1241 0.692 93 110
KRC164-4PH-C 452 48 80 670 500 647 390 745 40 165 951 877 25 927 0.373 51 56
KRC213-4PH-C 766 54 75 849 500 788 605 1020 62 220 1262 1165 38 1241 0.692 68 85
KRC317-4PH-C 766 54 75 954 500 915 605 1020 62 255 1262 1165 38 1241 0.692 93 110
KRC389-6PH-C 766 54 75 1004 500 965 605 1050 62 220 1675 1505 38 1581 1.014 129 153
KRC457-6PH-C 766 54 75 1004 750 965 605 1050 62 255 2408 2240 38 2316 2.55 158 248
KRC574-6PH-C 766 54 75 1004 750 965 605 1050 62 255 2408 2240 38 2316 2.55 186 276
KRC693-6PH-C 840 80 80 1107 750 1065 610 1050 18 440 3205 3003 44 3091 4.34 208 328
KRC861-6PH-C 840 80 80 1107 750 1065 610 1050 18 400 3205 3003 44 3091 4.34 263 383
⚠ Installation Dimension Notice
The A–W dimensions correspond to the dimensional drawings for top-ventilation and side-ventilation configurations in the KRC catalogue. Confirm the applicable arrangement before fabricating support structures or refrigeration pipework.

🧮 Condenser Selection Correction Factors

K0 – Discharge Temperature Correction
Discharge Temperature R404A R134a R410A R22
85°C 0.978 0.970 0.985 0.988
K1 – Ambient Temperature Correction
Ambient °C 15 20 25 30 35 40 45
Factor 0.979 0.986 0.992 0.998 1.003 1.008 1.013
K2 – Altitude Correction
Altitude m 0 600 800 1000 1200 1400 1600
Factor 1.00 1.04 1.06 1.075 1.09 1.11 1.12
K3 – Internal Subcooling Correction
Subcooling K KTD 3 KTD 5 KTD 10 KTD 15 KTD 20
2 0.966 0.976 0.989 0.994 0.996
4 — 0.934 0.975 0.986 0.990
6 — — 0.946 0.972 0.980
8 — — 0.898 0.960 0.966
K3 – Extra Subcooling Correction
Subcooling K 4 6 8 10
Factor 0.950 0.930 0.910 0.880
K4 – Refrigerant Correction Factor
Refrigerant R502 R134a R22 R410A R507 R407B R407C
Factor 0.96 0.93 0.95 1.02 0.98 0.92 0.90
K5 – Fin Correction Factor
Fin Material Correction Factor
Aluminium 1.00
Condenser Selection Formula

Required Condenser Standard THR
= [ K2 ÷ (K0 × K1 × K3 × K4 × K5) ] × Required Capacity

🏭 Typical Applications

🛒 Supermarkets

Remote condenser applications for supermarket refrigeration systems.

❄️ Cold Storage

Chilled and frozen cold rooms and commercial cold-storage facilities.

🧊 Freezer Rooms

Outdoor heat rejection for low-temperature refrigeration systems.

🍽️ Food Service

Central kitchens, food processing and commercial refrigeration installations.

🔍 Information Required for KRC Condenser Selection

1. Refrigerant R404A, R22, R134a, R410A or other applicable refrigerant.
2. Required Heat Rejection Condenser THR / required capacity.
3. Ambient Temperature Maximum outdoor design temperature.
4. Condensing Temperature Required saturated condensing temperature.
5. Installation Orientation Top ventilation or side ventilation.
6. Site Altitude Required for altitude correction.
7. Subcooling Confirm internal or additional subcooling requirement.
8. Noise Requirement Consider fan speed and acoustic requirements.
9. Electrical Supply Confirm available site voltage and phase.
⚠ Important Selection Notice
Condenser capacity is affected by refrigerant, ambient temperature, condensing temperature, altitude, subcooling and operating temperature difference.

Do not select a KRC condenser solely from the model number or nominal capacity. Final condenser selection should be checked against the actual refrigeration system operating conditions and applicable correction factors.

Need Help Selecting a Muller KRC Air Cooled Condenser?

Send RNA Engineering & Trading Sdn Bhd your refrigerant, required heat rejection, ambient temperature, condensing temperature, installation orientation and project operating conditions. Our team can assist with selecting a suitable Muller KRC condenser for your refrigeration system.

Technical information above is based on the supplied KRC Air Cooled Condenser catalogue. Specifications and available configurations should be reconfirmed before final order, equipment selection or fabrication.



 Inquiry - Muller KRC Air Cooled Condenser