Muller WRC Air Cooled Condenser



Muller WRC Series air-cooled condensers

Twenty-eight commercial condenser models built around a floating coil that moves with the heat instead of cracking under it. Top or side airflow, 800 mm fans, and heat rejection from 177 kW to 552 kW.

Supplied, selected and serviced in Malaysia by RNA Engineering & Trading Sdn. Bhd.

28models, WRC098 to WRC307LN
177–552 kWheat rejection, R404A at 18 K TD
2–5fans, 800 mm diameter
IP54electrical cabinet as standard

Built for rooftops that never cool down

The WRC series is a commercial remote condenser for supermarkets, cold storage and food service plant. It pairs a large-diameter 800 mm fan with a deep grooved-tube coil, so it moves the heat you need without spinning fast enough to become a noise complaint. Every model is available in a standard or low-noise fan configuration and can be installed for either top or side discharge.

Patented floating coil

The coil expands and contracts independently of the casing. Thermal movement never loads the tube joints, which is where rooftop condenser leaks normally begin.

Grooved tube coil

Internally grooved tubes increase the wetted surface and break up the refrigerant film, raising heat transfer for the same face area.

Two-speed motors

External rotor three-phase motors with built-in thermal protection and an integral header protection shield. Drop to low speed at night or in cool ambient and cut fan power by roughly 40 percent.

IP54 control panel

Fans arrive pre-wired to a weatherproof IP54 cabinet, so site work is a supply cable and a control signal rather than a wiring exercise.

Top or side airflow

The same model can discharge upward on Euro legs or horizontally against a wall. Units can also be banked side by side for larger duties.

Galvanised steel casing

Galvanised steel plain sheet as standard, with optional blue-fin coated coils for coastal and high-humidity sites.

 

How to read a WRC model number

WRC198LN-EM
WRCAir-cooled condenser series.
198Nominal heat rejection divided by 100. WRC198 is 19,800 W/K nominal.
LN8-pole low-noise motor. No suffix means the 6-pole standard motor.
EMEBM EC motor. Blank means a Ziehl-Abegg motor, which is the standard build.

Nominal capacity is stated at 0 K sub-cooling, 32 °C ambient, 50 °C condensing and 100 °C suction temperature on R404A.

Full specification tables

All 28 models are listed below. Type a model number, a capacity or a fan count to filter every table on the page at once.

Capacity and electrical data — standard condensers High speed 880 rpm, low speed 660 rpm. Capacity in W/K at 0 K sub-cooling, 32 °C ambient, 50 °C condensing, 100 °C suction.
Model R404A high
(W/K)
R22 high
(W/K)
Airflow high
(m³/h)
R404A low
(W/K)
R22 low
(W/K)
Airflow low
(m³/h)
Fans Power hi/lo
(W)
Max current hi/lo
(A)
Duty @18 K
(kW)
WRC098 9,840 9,350 44,244 8,360 7,950 37,620 2 4,000 / 2,500 8 / 4.6 177
WRC112 11,210 10,650 40,890 9,190 8,730 30,384 2 4,000 / 2,500 8 / 4.6 202
WRC119 11,860 11,270 38,232 9,610 9,130 28,008 2 4,000 / 2,500 8 / 4.6 213
WRC123 12,310 11,690 36,036 9,850 9,350 26,136 2 4,000 / 2,500 8 / 4.6 222
WRC147 14,750 14,010 66,384 12,540 11,910 56,412 3 6,000 / 3,750 12 / 6.9 266
WRC167 16,740 15,900 61,344 13,730 13,040 45,576 3 6,000 / 3,750 12 / 6.9 301
WRC178 17,760 16,870 56,628 14,390 13,660 41,472 3 6,000 / 3,750 12 / 6.9 320
WRC185 18,460 17,540 54,036 14,770 14,030 39,168 3 6,000 / 3,750 12 / 6.9 332
WRC198 19,790 18,800 88,488 16,820 15,980 75,204 4 8,000 / 5,000 16 / 9.2 356
WRC225 22,470 21,350 81,792 18,430 17,510 60,168 4 8,000 / 5,000 16 / 9.2 404
WRC240 23,970 22,770 76,500 19,420 18,440 56,016 4 8,000 / 5,000 16 / 9.2 431
WRC247 24,650 23,420 72,036 19,720 18,740 52,236 4 8,000 / 5,000 16 / 9.2 444
WRC297 29,710 28,220 95,616 24,070 22,860 70,020 5 10,000 / 6,250 20 / 11.5 535
WRC307 30,690 29,160 90,036 24,550 23,330 65,268 5 10,000 / 6,250 20 / 11.5 552
No standard models match that search.
Capacity and electrical data — low-noise (LN) condensers High speed 680 rpm, low speed 530 rpm. Same rating basis as the standard range.
Model R404A high
(W/K)
R22 high
(W/K)
Airflow high
(m³/h)
R404A low
(W/K)
R22 low
(W/K)
Airflow low
(m³/h)
Fans Power hi/lo
(W)
Max current hi/lo
(A)
Duty @18 K
(kW)
WRC098LN 8,430 8,010 33,912 7,570 7,190 26,784 2 2,100 / 1,540 4.8 / 3 152
WRC112LN 9,490 9,020 31,536 8,190 7,790 24,660 2 2,100 / 1,540 4.8 / 3 171
WRC119LN 9,880 9,390 29,340 8,410 7,990 22,572 2 2,100 / 1,540 4.8 / 3 178
WRC123LN 9,990 9,490 27,504 8,380 7,960 20,916 2 2,100 / 1,540 4.8 / 3 180
WRC147LN 12,640 12,010 50,868 11,350 10,780 40,176 3 3,150 / 2,310 7.2 / 4.5 228
WRC167LN 14,220 13,510 47,304 12,270 11,660 36,972 3 3,150 / 2,310 7.2 / 4.5 256
WRC178LN 14,860 14,120 44,028 12,640 12,020 33,876 3 3,150 / 2,310 7.2 / 4.5 267
WRC185LN 15,010 14,260 41,256 12,600 11,970 31,392 3 3,150 / 2,310 7.2 / 4.5 270
WRC198LN 17,060 16,210 67,824 15,320 14,560 53,568 4 4,200 / 3,080 9.6 / 6 307
WRC225LN 19,000 18,050 63,072 16,400 15,580 49,320 4 4,200 / 3,080 9.6 / 6 342
WRC240LN 19,790 18,800 58,680 16,840 16,000 45,144 4 4,200 / 3,080 9.6 / 6 356
WRC247LN 19,990 18,990 55,008 16,780 15,940 41,832 4 4,200 / 3,080 9.6 / 6 360
WRC297LN 24,730 23,490 73,368 21,040 19,990 56,448 5 5,250 / 3,850 12 / 7.5 445
WRC307LN 25,010 23,760 68,796 20,990 19,940 52,344 5 5,250 / 3,850 12 / 7.5 450
No low-noise models match that search.

Supply is 380 V / 3 phase throughout. Listed power and current are the maximum values the external rotor motor may draw; actual figures vary with supply voltage, condenser layout and fin cleanliness but will not exceed these. Duty at 18 K is the R404A high-speed figure multiplied by an 18 K condensing temperature difference, given as an indication only.

Dimensions and weights All dimensions in mm. Length, A, B and C are identical for both airflow orientations; only casing width and height change.
Model L W top vent H top vent W side vent H side vent A B C Transport (m³) Net (kg) Packed (kg)
WRC098LN 3,260 1,250 1,410 1,136 1,250 2,750 6.7 410 440
WRC112LN 3,260 1,250 1,410 1,136 1,250 2,750 6.7 430 460
WRC119LN 3,260 1,250 1,410 1,136 1,250 2,750 6.7 460 490
WRC123LN 3,260 1,250 1,410 1,136 1,250 2,750 6.7 500 530
WRC147LN 4,660 1,250 1,410 1,136 1,250 4,150 2,775 1,375 8.7 560 600
WRC167LN 4,660 1,250 1,410 1,136 1,250 4,150 2,775 1,375 8.7 610 650
WRC178LN 4,660 1,250 1,410 1,136 1,250 4,150 2,775 1,375 8.7 660 700
WRC185LN 4,660 1,250 1,410 1,136 1,250 4,150 2,775 1,375 8.7 710 750
WRC198LN 6,068 1,250 1,410 1,136 1,250 5,550 2,775 11.7 740 800
WRC225LN 6,068 1,250 1,410 1,136 1,250 5,550 2,775 11.7 820 880
WRC240LN 6,068 1,250 1,410 1,136 1,250 5,550 2,775 11.7 890 950
WRC247LN 6,068 1,250 1,410 1,136 1,250 5,550 2,775 11.7 960 1,020
WRC297LN 7,469 1,250 1,410 1,136 1,250 6,950 2,775 1,400 13.7 1,130 1,200
WRC307LN 7,469 1,250 1,410 1,136 1,250 6,950 2,775 1,400 13.7 1,210 1,290
No models match that search.

Mounting hole pitch is 1,065 mm on top-ventilation units and 1,035 mm on side-ventilation units. Header projection is 133 mm. Dimensions are published for the single-row LN casings; standard-speed models share the same casing sizes. Confirm certified drawings with RNA before steelwork is fabricated.

 
Coil rows, refrigerant charge and connection sizes Fin spacing 12 FPI on all standard builds. Charge is the pump-down volume at 32 °C, based on 80 percent liquid and 20 percent gas by coil volume.
Model Coil rows FPI R404A charge (kg) Inlet (mm) Outlet (mm)
Standard condensers
WRC098 3 12 29 54.4 54.4
WRC112 4 12 37 54.4 54.4
WRC119 5 12 45 54.4 54.4
WRC123 6 12 53 54.4 54.4
WRC147 3 12 43 66.7 66.7
WRC167 4 12 55 66.7 66.7
WRC178 5 12 67 66.7 66.7
WRC185 6 12 79 66.7 66.7
WRC198 3 12 54 66.7 66.7
WRC225 4 12 70 66.7 66.7
WRC240 5 12 86 66.7 66.7
WRC247 6 12 102 66.7 66.7
WRC297 5 12 106 66.7 66.7
WRC307 6 12 126 66.7 66.7
Low-noise condensers
WRC098LN 3 12 29 54.4 54.4
WRC112LN 4 12 37 54.4 54.4
WRC119LN 5 12 45 54.4 54.4
WRC123LN 6 12 53 54.4 54.4
WRC147LN 3 12 43 66.7 66.7
WRC167LN 4 12 55 66.7 66.7
WRC178LN 5 12 67 66.7 66.7
WRC185LN 6 12 79 66.7 66.7
WRC198LN 3 12 54 66.7 66.7
WRC225LN 4 12 70 66.7 66.7
WRC240LN 5 12 86 66.7 66.7
WRC247LN 6 12 102 66.7 66.7
WRC297LN 5 12 106 66.7 66.7
WRC307LN 6 12 126 66.7 66.7
No models match that search.
Sound data Sound pressure measured at 3 m from the fan plane, to ISO 9614-1 and AS 1217.7-1985. Site reflection will change what you measure.
Models Lw high dB(A) Lp 3 m high dB(A) Lw low dB(A) Lp 3 m low dB(A)
Standard condensers — 880 / 660 rpm
WRC098 – WRC123 86 69 81 64
WRC147 – WRC185 88 71 83 64
WRC198 – WRC247 89 72 84 67
WRC297 – WRC307 90 73 85 68
Low-noise condensers — 680 / 530 rpm
WRC098LN – WRC123LN 79 62 76 59
WRC147LN – WRC185LN 81 63 78 60
WRC198LN – WRC247LN 82 65 79 62
WRC297LN – WRC307LN 83 66 80 63
No models match that search.

Options and standard build

WRC configuration matrix ● standard    ○ optional    ✕ not available
Item Option WRC
Motor Ziehl-Abegg motor
Motor EBM EC motor
Motor Interlink motor
Fin Fin coating, blue fin
Casing Galvanised steel plain sheet
Casing Stainless steel
Fin spacing 12 FPI (2.12 mm)
Fin spacing 10 FPI (2.54 mm)
Fin spacing 9 FPI (2.82 mm)
Other Fan wiring
Other Electrical cabinet, IP54
Other Two banks condenser

Wider fin spacing at 10 or 9 FPI is worth specifying for dusty sites, bakeries and anywhere the coil cannot be washed often. Blue-fin coating is the usual choice for coastal installations. If you need an accessory that is not listed here, ask RNA and we will check it with the factory.

 

Selecting the right model

Published capacity is stated in watts per kelvin, so it scales directly with the condensing temperature difference you design for. Before comparing that figure against your duty, correct it for site conditions.

Required condenser standard THR = K2 ÷ (K1 × K3 × K4) × required capacity
Correction factors
Factor Applies to Range
K1 Ambient temperature 0.979 at 15 °C → 1.013 at 45 °C
K2 Altitude 1.00 at sea level → 1.12 at 1,600 m
K3 Internal sub-cooling 0.898 to 0.996, depending on sub-cooling and KTD
K4 Fin type 1.00 aluminium, 0.995 blue fin
K1 — ambient temperature
Ambient °C 15 20 25 30 35 40 45
Factor 0.979 0.986 0.992 0.998 1.003 1.008 1.013
K2 — altitude
Altitude m 0 600 800 1,000 1,200 1,400 1,600
Factor 1 1.04 1.06 1.075 1.09 1.11 1.12
K3 — internal sub-cooling Read against the condensing temperature difference, KTD.
Sub-cooling K KTD 3 KTD 5 KTD 10 KTD 15 KTD 20
2 0.966 0.976 0.989 0.994 0.996
4 0.934 0.975 0.986 0.990
6 0.946 0.972 0.980
8 0.898 0.960 0.966

Worked example

  1. Duty required: 300 kW heat rejection on R404A at a 15 K condensing temperature difference.
  2. Capacity needed in W/K: 300,000 ÷ 15 = 20,000 W/K.
  3. Site is Selangor at 35 °C ambient and near sea level, 4 K sub-cooling, aluminium fins. K1 = 1.003, K2 = 1.00, K3 = 0.986, K4 = 1.00.
  4. Corrected requirement: 1.00 ÷ (1.003 × 0.986 × 1.00) × 20,000 = 20,229 W/K.
  5. Standard range: WRC225 at 22,470 W/K clears it with margin. Low-noise range: WRC240LN at 19,790 W/K is marginally short, so step up to WRC247LN or WRC297LN.

The KTD in these tables is the saturated liquid temperature at the condenser outlet minus the inlet air temperature. Capacity figures assume all fans are running. Send us your duty, refrigerant and site conditions and we will run the selection for you.

Where the WRC series is used

Supermarkets and hypermarkets

Remote condensers for medium and low temperature packs, where roof space is shared with tenants and plant noise is regulated.

Cold storage and distribution

High ambient duty for chilled and frozen chambers, blast rooms and loading docks, with wider fin spacing available for dusty yards.

Food service and central kitchens

Compact two and three fan models for restaurant, hotel and catering plant rooms where the condenser sits close to occupied areas.

Process and industrial cooling

Multiple units banked side by side for larger process loads, using the same coil block and control approach across the plant.

Common questions

What does the floating coil design actually do?

The coil is allowed to expand and contract independently of the casing. Thermal movement is absorbed by the mounting instead of being transferred into the tube joints, which is where coil leaks normally start on a rooftop condenser. The result is a longer coil service life and fewer refrigerant losses over the life of the plant.

Standard or low noise — which should I specify?

Standard models run at 880 rpm high speed and 660 rpm low speed. LN models run at 680 rpm and 530 rpm and are roughly 6 to 7 dB(A) quieter in sound power. The trade-off is airflow: an LN model of the same size rejects less heat, so for a given duty you generally step up one or two model sizes. Where the condenser sits near residential boundaries or hotel rooms, the LN range is usually the cheaper answer once acoustic treatment is priced in.

Which refrigerants are covered?

Published capacity data covers R404A and R22. R404A is the rating basis. For other refrigerants, or for the KRC range which also publishes R134a and R410A data, contact RNA and we will confirm the selection with the factory.

Can units be installed side by side?

Yes. Multiple units can be banked in parallel, and a two-bank condenser is available as a factory option. Maintain the manufacturer's minimum clearance around each unit so that discharge air is not drawn back into the coil, which is the most common cause of high head pressure on a correctly sized condenser.

What is included as standard on delivery?

Galvanised steel casing, aluminium fins at 12 FPI, Ziehl-Abegg two-speed external rotor motors with built-in thermal protection, factory fan wiring, and an IP54 electrical cabinet. Blue-fin coating, EC motors, wider fin spacing and two-bank arrangements are ordered as options.

Do you supply and install in Malaysia?

RNA Engineering & Trading Sdn. Bhd. supplies the WRC range across Malaysia with selection support, commissioning advice and after-sales service. Tell us the duty and site conditions and we will come back with a model, a drawing and a price.

Send us the duty, we will send back the selection

Give us your heat rejection, refrigerant, design ambient and any noise limit. We will confirm the model, issue a certified drawing and quote delivery.

Technical data reproduced from the manufacturer's WRC series catalogue. Specifications are subject to change without notice. Capacities, dimensions and electrical data must be confirmed against certified documents before order or fabrication. RNA Engineering & Trading Sdn. Bhd., Malaysia.